TPI DC711-View Flue Gas Analyser Kit
The TPI DC711-View Flue Gas Analyser Kit gives gas heating engineers and installers a View-enabled DC711 analyser in a ready-to-use kit format. The kit includes the DC711 analyser, probe and charger supplied in a padded carry case.
TPI positions the DC711-View for domestic or commercial use. It supports multiple fuel options and conforms to EN50379 Parts 1-3. In addition, it includes pressure and tightness testing, differential temperature measurement and TPI View App functionality.
Efficient Testing and Reporting
The DC711-View supports hold, save, print and send functions, so engineers can manage readings clearly during a job. It also includes a clear, easy to read screen and an easy to navigate menu system.
Use the analyser with or without the TPI View App. When used with the app, TPI View connects to compatible smart devices via Bluetooth and can show live results on a smartphone or tablet. It also allows users to save, email or print reports, while time, date and GPS stamped results help document when and where the job took place.
Built for Field Use
The DC711-View uses a backlit graphic LCD and a Li-ion 3.7V battery with more than 6 hours of battery life. It also uses a USB-C type charger input and operates from 14°F to +122°F, which is listed by TPI as -10°C to +50°C.
Key Features
- View-enabled DC711 flue gas analyser kit
- Designed for gas heating engineers and installers
- Suitable for domestic or commercial use
- Multiple fuel options
- Hold, save, print and send functions
- Clear, easy to read screen
- Easy to navigate menu system
- Pressure and tightness test feature
- Differential temperature for flow and return or radiator balancing
- Conforms to EN50379 Parts 1-3
Technical Specifications
| SKU | TPI/DC711-View Kit |
|---|---|
| Operating temperature range | 14°F to +122°F (-10°C to +50°C) |
| Battery / battery life | Li-ion 3.7V / > 6 hours |
| Charger input | USB-C type |
| Fuels | Natural Gas, LPG, Light Oil, Heavy Oil, Bituminous Coal, Anthracite Coal, Coke, Butane, Wood, Bagasse |
| Pressure ranges | mbar, psi, inH2O, mmH2O, kPa, hPa, inHg, mmHg, mH2O |
| Display | Backlit Graphic LCD |
| Data storage | 100 sets of readings, 30 sets for CO Build Up, multiple pages |
| Time and date | 24 Hour Real Time Clock |
| Dimensions | 7.28” (185mm) x 4.92” (125mm) x 2.56” (65mm) |
| Weight | 1.83lbs (830g) |
| Conforms to | EN50379 Parts 1-3 |
| Flue temperature probe construction | Pistol Grip with Stainless Steel Shaft |
| Flue temperature probe hose length | 8.2’ (2500mm) |
| Flue temperature probe insertion length | 7.9” (200mm) |
| K-Type thermocouple accuracy | +/- 0.3% of fullscale, +/- 2°F (1°C) |
| Flue temperature probe maximum temperature | 1472°F (800°C) |
| Oxygen | Range: 0-25%; resolution: 0.1%; accuracy: +/- 0.3% |
| Carbon Monoxide (low) | Range: 0-10,000 ppm; resolution: 1 ppm (<100ppm); accuracy: +/- 5 ppm (<100ppm), +/- 5% (>=100ppm) |
| Carbon Dioxide | Range: 0-25%; resolution: 0.1%; calculated |
| CO/CO2 Ratio | Range: 0-0.999; resolution: 0.001; calculated |
| Combustion Efficiency | Range: 0-100%; resolution: 0.1%; calculated |
| Pressure measurement selectable ranges | mbar, psi, inH2O, mmH2O, kPa, hPa, inHg, mmHg, mH2O |
| Pressure measurement range | -150 mbar to +150 mbar; -15 kPa to +15 kPa; -60 inH2O to 60 inH2O |
| Pressure measurement resolution | 0.001 mbar (0~9.999 mbar); 0.01 mbar (10.00~149.99 mbar) |
| Pressure measurement accuracy | +/- 0.5 mbar FSD |
| Temperature measurement input type | K-Type thermocouple |
| Temperature measurement range | -58°F to 1832°F (-50°C to 1000°C)* |
| Temperature measurement resolution | 1°F (1°C) |
| Temperature measurement accuracy | +/- (0.3% of rdg + 2°F) or +/- (0.3% of rdg + 1°C) |
What’s Included
- View enabled DC711 Analyser
- Probe
- Charger
- Padded Carry Case