The Martindale EPAT2100 Dual Voltage Manual PAT Tester provides a simple and effective way to carry out portable appliance testing on both 110V and 230V equipment. Its one-button operation helps users complete routine inspections quickly and consistently. Clear test functions make it suitable for a wide range of workplace environments.
Designed for Class I and Class II appliance testing, this tester performs earth bond and insulation resistance checks while also offering run current, leakage current and flash testing. It supports both standard and more demanding testing requirements. As a result, maintenance teams can complete several test procedures with a single instrument.
Dual Voltage Testing Capability
Unlike single-voltage alternatives, the Martindale EPAT2100 Dual Voltage Manual PAT Tester operates from either a 110V or 230V supply. This allows testing of equipment commonly found on construction sites, industrial facilities and commercial premises. It also enables run current and leakage tests without requiring an external power source.
High and low current earth bond testing adds further flexibility. Users can select 25A or 8A for standard earth continuity testing, while the 200mA option allows safer testing of sensitive IT and electronic equipment. This helps reduce the risk of damage during inspection procedures.
Comprehensive PAT Test Functions
Built-in flash testing expands the capability of the unit beyond standard PAT requirements. The tester can perform flash tests at 1.5kV AC for Class I appliances and 3.0kV AC for Class II appliances. Dedicated indicators provide clear status information during testing and help improve user confidence.
For added convenience, the unit includes a lead testing facility for IEC power leads and is supplied with accessories for testing mains extension leads. Two set types are available, allowing users to select the package best suited to their testing requirements. The compact design and straightforward controls make the tester easy to transport and operate in busy working environments.
Key Features
- Tests both 110V and 230V appliances
- One-button manual PAT testing operation
- Suitable for Class I and Class II appliances
- Performs insulation resistance testing
- Performs earth continuity testing
- Provides run current measurement
- Measures earth leakage current
- Integrated flash testing function
- Supports sensitive equipment testing at 200mA
- Built-in IEC lead testing capability
- Supplied with accessories for extension lead testing
- Mains powered from 110V or 230V supplies
- Displays test values during operation
- Automatic test mode for straightforward use
- Two set types available to suit application requirements
Technical Specifications
| Manufacturer | Martindale Electric |
| Model | EPAT2100 |
| Product name | Martindale EPAT2100 Dual Voltage Manual PAT Tester |
| Manufacturer part code | EPAT2100 |
| Supply voltage | 110V / 230V ±10% |
| Supply frequency | 50/60Hz |
| Power consumption | 10VA / 220VA |
| Appliance types | Class I and Class II |
| Insulation test voltage | 500V DC -0% +20% |
| Insulation test range | 0 to 19.9MΩ |
| Insulation accuracy | ±5% of reading ±1 digit |
| Insulation short circuit current | 1.5mA DC nominal |
| Earth continuity test currents | 200mA, 8A and 25A |
| Run current range | 0 to 19.9A |
| Run current accuracy | ±10% of reading ±1 digit |
| Earth leakage range | 0 to 19.9mA |
| Earth leakage accuracy | ±10% of reading ±1 digit |
| Flash test voltage Class I | 1.5kV AC |
| Flash test voltage Class II | 3.0kV AC |
| Flash test display range | 0 to 19.9mA AC |
| Flash test usable range | 0 to 3.5mA AC |
| Flash test trip current | 4mA nominal |
| Flash test accuracy | ±5% of reading ±1 digit |
| Earth continuity lead length | 1.5m |
| Mains socket | 240V 13A to BS1363 |
| 110V socket | 110V 16A to BS4343 |
| Flash socket | 4mm high safety socket |
| Indicators | Neon lamp, red LED over-temperature indicator and polarity LEDs |
| Compliance | BS EN 61010-1 |
| Dimensions | 330 x 263 x 144mm |
| Weight | 5.1kg |
| EAN | 5036162184482 |
| 110V adaptor included | Yes, TL150 adaptor supplied |
| Warranty | Not specified |
Comparison Table
| EPAT1600 | EPAT2100 | MPATPLUS | |
| Class I / II Test | ✓ | ✓ | ✓ |
| Lead Test | ✓ | ✓ | With accessory |
| Test Values Displayed | ✓ | ✓ | ✓ |
| Test Mode | Auto | Auto | Auto / Manual |
| Run Test | ✓ | ✓ | ✓ |
| Earth Continuity Test Current | 200mA / 8A / 25A | 200mA / 8A / 25A | 200mA / 25A |
| Insulation Test Voltage | 500V | 500V | 500V |
| 110V Appliances | ✓ | ✓ | ✓ |
| Flash Test | – | 1.5kV / 3kV | 1.5kV / 3kV |
| Memory | – | – | 1000 results for download |
| Supply | 230V | 230V / 110V | 230V / 110V |
Document Downloads
What’s Included
- Martindale EPAT2100 Dual Voltage Manual PAT Tester
- TL150 110V adaptor
- Earth continuity lead
- IEC lead testing facility
- Accessories for extension lead testing