- Designed for electrical contractor testing
- Five insulation test voltages up to 1000 V
- Automatic PI and DAR testing calculations
- Compare function supports pass/fail testing
Fluke 1507 Insulation Resistance Tester
Built for electrical contractors and industrial and commercial electricians, the Fluke 1507 Insulation Resistance Tester is a compact handheld instrument for advanced industrial and electrical insulation testing. It measures insulation resistance from 0.01 MΩ to 10 GΩ and provides five selectable test voltages of 50 V, 100 V, 250 V, 500 V and 1000 V for troubleshooting, commissioning and preventative maintenance work. Its compact size and light weight make the tester easy to pack and use.
Beyond insulation resistance, the tester measures AC/DC voltage from 0.1 V to 600 V and earth-bond resistance from 0.01 Ω to 20.00 kΩ with a 200 mA short-circuit current. Automatic Polarization Index and Dielectric Absorption Ratio calculations, a Compare pass/fail function, live circuit detection, auto-discharge, a remote test probe and a large backlit display support repetitive and hard-to-reach testing while keeping key results visible. It is rated CAT IV 600 V and runs on four AA batteries (NEDA 15A or IEC LR6).
Key Benefits
- Five test voltages support insulation testing from 50 V through to 1000 V
- Automatic PI and DAR calculations save time during timed insulation tests
- Compare function provides a selectable pass/fail limit for repetitive insulation measurements
- Live circuit detection inhibits insulation testing when terminal voltage exceeds 30 V
- Auto-discharge releases capacitive voltage through the tester after insulation testing
- Remote test probe supports repetitive and hard-to-reach measurements
- Large backlit display keeps measured values visible during use
- Auto power off helps conserve battery power between measurements
Common Applications
Fluke 1507 is suitable for a range of verified insulation testing tasks, including:
- Electrical insulation testing
- Industrial insulation testing
- Troubleshooting
- Commissioning
- Preventative maintenance
Why Choose This Model?
The Fluke 1507 suits users who need a stand-alone insulation tester with five test voltages, a 0.01 MΩ to 10 GΩ insulation range, PI/DAR testing and pass/fail comparison. The Fluke 1503 is positioned for basic insulation testing with 500 V and 1000 V test voltages, while the Fluke 1587 FC combines insulation testing with full multimeter functions and Fluke Connect features.
Product Comparison
| Feature | Fluke 1507 | Fluke 1503 | Fluke 1587 FC |
|---|---|---|---|
| Product type | Stand-alone insulation tester | Stand-alone insulation tester | Insulation multimeter |
| Recommended for | Electrical contractors, industrial and commercial electricians | Residential and commercial electricians | Industrial plant maintenance, industrial and utilities electricians, field service contractors and commercial HVAC/R technicians |
| Test voltages | 50 V, 100 V, 250 V, 500 V, 1000 V | 500 V, 1000 V | 50 V, 100 V, 250 V, 500 V, 1000 V |
| Insulation resistance range | 0.01 MΩ to 10 GΩ | 0.01 MΩ to 2000 MΩ | 0.01 MΩ to 2 GΩ |
| PI/DAR | ✓ | No | ✓ |
| Pass/fail comparison | ✓ | No | No |
| Remote test probe | ✓ | ✓ | ✓ |
| Display | Digital LCD | Digital LCD | Digital LCD |
General Specifications
| Specification | Details |
|---|---|
| Product type | Battery-powered handheld insulation tester |
| Display | Large backlit display |
| Test lock | Locks an active insulation test until the lock or test button is pressed again |
| PI/DAR function | Automatic Polarization Index and Dielectric Absorption Ratio calculation |
| Compare function | Selectable pass/fail compare levels from 100 kΩ to 500 MΩ |
| Live circuit detection | Inhibits insulation testing if terminal voltage is >30 V before test initiation |
| Auto discharge | Discharge time <0.5 second for C = 1 μF or less |
| Maximum voltage applied to any terminal | 600 V AC rms or DC |
| Safety | Measurement category IV 600 V (CAT IV) |
| Safety standards | ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04 and IEC/EN 61010-1 2nd Edition |
| Certifications | CSA per standard CSA/CAN C22.2 No. 61010.1-04; TUV per standard IEC/EN 61010-1 2nd Edition |
| Ingress protection | IP40 |
| Power supply | Four AA batteries (NEDA 15A or IEC LR6) |
| Auto power off | Sleep mode after 10 minutes without a function change or button press |
| Optional hanging system | Accepts the optional Fluke TPAK magnetic hanging system |
Measurement and Accuracy Specifications
| Measurement Function | Range and Resolution | Accuracy |
|---|---|---|
| AC/DC voltage | 600.0 V range 0.1 V resolution |
± (2 % + 3), 50 Hz to 400 Hz |
| Earth-bond resistance | 20.00 Ω / 0.01 Ω 200.0 Ω / 0.1 Ω 2000 Ω / 1 Ω 20.00 kΩ / 0.01 kΩ |
± (1.5 % + 3) |
| Insulation resistance, 50 V dc | 0.01 to 20.00 MΩ / 0.01 MΩ 20.0 to 50.0 MΩ / 0.1 MΩ |
± (3 % + 5) |
| Insulation resistance, 100 V dc | 0.01 to 20.00 MΩ / 0.01 MΩ 20.0 to 100.0 MΩ / 0.1 MΩ |
± (3 % + 5) |
| Insulation resistance, 250 V dc | 0.01 to 20.00 MΩ / 0.01 MΩ 20.0 to 200.0 MΩ / 0.1 MΩ |
± (1.5 % + 5) |
| Insulation resistance, 500 V dc | 0.01 to 20.00 MΩ / 0.01 MΩ 20.0 to 200.0 MΩ / 0.1 MΩ 200 to 500 MΩ / 1 MΩ |
± (1.5 % + 5) |
| Insulation resistance, 1000 V dc | 0.1 to 200.0 MΩ / 0.1 MΩ 200 to 2000 MΩ / 1 MΩ 2.0 to 10.0 GΩ / 0.1 GΩ |
± (1.5 % + 5) to 2000 MΩ ± (10 % + 3) from 2.0 to 10.0 GΩ |
| Insulation test voltage | 50 V, 100 V, 250 V, 500 V, 1000 V dc | +20 %, -0 % |
Mechanical and General Information
| Specification | Details |
|---|---|
| Operating temperature | -20°C to 55°C (-4°F to 131°F) |
| Storage temperature | -40°C to 60°C (-40°F to 140°F) |
| Relative humidity | 0% to 95% @ 10°C to 30°C (50°F to 86°F) 0% to 75% @ 30°C to 40°C (86°F to 104°F) 0% to 40% @ 40°C to 55°C (104°F to 131°F) |
| Temperature coefficient | 0.05 x (specified accuracy) per °C for temperatures <18°C or >28°C (<64°F or >82°F) |
| Dimensions (H x W x L) | 5.0 x 10.0 x 20.3 cm (1.97 x 3.94 x 8.00 in) |
| Weight | 550 g (1.2 lb) |
| Operating altitude | 2000 m CAT IV 600 V, 3000 m CAT III 600 V |
| Non-operating altitude | 12,000 m |
| Vibration | Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument |
| Shock | 1 meter drop per IEC 61010-1 2nd Edition (1 meter drop test, six sides, oak floor) |
| Battery life, insulation testing | At least 1000 insulation tests with fresh alkaline batteries at room temperature |
| Battery life, earth-bond resistance | At least 2500 earth-bond resistance measurements with fresh alkaline batteries at room temperature |
Specification Notes
- Earth-bond resistance accuracies apply from 0 to 100% of range
- Insulation test battery life is based on 1000 V into 1 MΩ with a 5 second on and 25 second off duty cycle at room temperature
- Earth-bond battery life is based on 1 Ω with a 5 second on and 25 second off duty cycle at room temperature
What’s Included
- Fluke 1507 Insulation Resistance Tester
- Remote probe
- TL224 Test Leads
- TP74 Test Probes
- Alligator clips
- Holster
- User documentation
Meta Description
Fluke 1507 Insulation Resistance Tester for advanced insulation testing, with five test voltages, PI/DAR calculations and Compare function.
Official Documents
What’s Included
- Fluke 1507 Insulation Resistance Tester
- Remote probe