- Built for electricians and electrical tests
- Measures from 12 to 1000 V AC and 1500 V DC
- Voltage indication works without batteries
- Phase rotation and continuity test functions
Megger TPT420 Two-Pole Voltage Tester
Built for electricians and electrical engineers, the Megger TPT420 Two-Pole Voltage Tester provides AC and DC voltage measurement across low-voltage installations. Its LED and four-digit LCD displays indicate from 12 to 1000 V AC and 12 to 1500 V DC, while automatic polarity indication and a backlight support clear reading. A dangerous-voltage warning remains available when the batteries are exhausted, although this function must not be used for measurement purposes.
Beyond voltage testing, the instrument provides continuity indication from 0 to 500 kΩ, a diode test, single-pole phase testing and phase-rotation indication. Its phase-rotation function avoids crossing the test probes, while measurements between phase and earth are designed to remain below the tripping threshold of RCDs, RCBOs and safety breakers. An integrated LED torch assists in poorly lit environments, while the CAT IV 1000 V rating, IP64 housing and supplied GS38 shrouds support use under the stated electrical test conditions.
Key Benefits
- LED and LCD displays provide stepped voltage indication and a digital reading
- Dangerous-voltage warning remains available when the batteries are exhausted
- Continuity testing provides both visual and acoustic indication
- Simplified phase-rotation testing avoids crossing the test probes
- Low input current helps avoid unintentional disconnection of RCD, RCBO and safety-breaker protected circuits
- Single-pole phase testing provides an additional voltage-indication function
- Automatic power control switches the tester on when a supported signal is detected
- Integrated LED torch supports work in poorly lit environments
- Self-test function checks that the batteries can power the tester correctly
- CAT IV 1000 V rating and IP64 protection support use within the stated conditions
Common Applications
The Megger TPT420 is suitable for a range of electrical testing tasks, including:
- AC voltage measurement
- DC voltage measurement
- Continuity testing
- Testing within electrical installations
- Automotive electrical testing
- Fire alarm system testing
- Solar and PV system testing
General Specifications
| Specification | Details |
|---|---|
| Product type | Two-pole voltage tester |
| Display | 13 LEDs and four-digit LCD |
| Backlight | Automatic |
| Polarity indication | Automatic LED indication for AC, positive DC and negative DC |
| Voltage indication without batteries | Voltage warning LED operates when dangerous voltage is present, including when the batteries are exhausted; this function must not be used for measurement |
| Acoustic indication | Sounder accompanies voltage and continuity indication; voltage threshold is approximately 38 V AC or 100 V DC |
| Single-pole phase test | 100 to 1000 V AC at 50/60 Hz |
| Rotation field test | 170 to 1000 V AC at 50/60 Hz, with left and right rotary-field indication |
| Diode test | Visual and acoustic indication according to diode orientation |
| Auto-power-on | Activates when continuity, AC or DC voltage above approximately 10 V, or a live phase at L2 is detected; also activates through the torch button |
| Auto-power-off | Approximately 5 seconds after no signal is detected; torch switches off after approximately 10 seconds |
| Self-test | Continuity LED and continuous audible tone confirm sufficient battery power when the probe tips are shorted together |
| Peak current | Is <3.5 mA at 1000 V |
| Input current | <3.5 mA at 690 V AC <6 mA at 1500 V DC |
| Electrical measurement category | CAT IV 1000 V |
| Safety standards | IEC/EN 61243-3 and DIN VDE 0682-401 |
| EMC standard | EN 61326-1 |
| Ingress protection | IP64 |
| Pollution degree | 2 |
| Power supply | 2 x 1.5 V AAA batteries, IEC R03 |
Measurement and Accuracy Specifications
| Measurement Function | Range and Resolution | Accuracy |
|---|---|---|
| AC voltage | Range: 12 to 1000 V AC Resolution: 1 V Frequency range: 40 to 400 Hz |
±3% ±5 dgt |
| DC voltage | Range: 12 to 1500 V DC Resolution: 1 V Polarity: DC(±) |
±3% ±5 dgt |
| LED voltage indication | Nominal voltages: ±12, 24, 50, 120, 230, 400, 690 and 1000 V Response time: <1 s at 100% of each nominal voltage |
LED tolerances according to EN 61243-3 |
| Continuity | 0 to 500 kΩ Visual and acoustic indication No continuity measurement on the LCD |
Threshold tolerance: +50% |
Mechanical and General Information
| Specification | Details |
|---|---|
| Dimensions | 67 mm (W) x 205 mm (L) x 19 mm (D) |
| Weight | 180 g |
| Probe lead length | 1.2 m |
| Operating temperature | -5 to 40 °C, with no condensation |
| Storage temperature | -20 to 70 °C, with no condensation |
| Humidity | Maximum 85% RH |
| Maximum altitude | Up to 2000 m |
| Probe features | Main probe, remote probe, hand barriers, GS38 UK tips and Euro tips |
| Measurement light | Integrated LED torch |
Specification Notes
- Datasheet specifications are stated at 23 °C ±5 °C and ≤80% RH
- Measurement duty is 30 seconds on followed by a 240-second recovery period
- Single-pole phase testing must not be the sole verification of a live circuit, and effective phase-rotation results require a three-phase four-wire system
What’s Included
- Protective pouch, 2005-536
- GS38 probe-tip shrouds
- 2 x AAA batteries
Meta Description
Megger TPT420 Two-Pole Voltage Tester measures 12 to 1000 V AC and 12 to 1500 V DC, with phase rotation and continuity indication.

Reviews